GF Signet 3-9900-1 Flow Multi-Parameter Controller
GF Signet 3-9900-1 9900 SmartPro® Transmitter with Panel Mount
Signet 3-9900-1 Flow Multi-Parameter Controller with Field Mount Transmitter Measurement Types : Flow, pH/ORP, Conductivity/Resistivity, Salinity, Pressure, Temperature, Level, Dissolved Oxygen, Batch or user-defined (via 8058)
The Signet 9900 Transmitter provides a single channel interface for many different parameters including Flow, pH/ORP, Conductivity/Resistivity, Salinity, Pressure, Temperature, Level and other sensors that output a 4 to 20 mA signal. The 9900 Transmitter (Generation III) has the added capability of supporting the Batch Module for batching control the extra large (3.90" x 3.90") auto-sensing backlit display features "at-a-glance" visibility that can be viewed at 4-5 times the distance over traditional transmitters. The highly illuminated display and large characters reduce the risk of misreading or misinterpreting the displayed values. The display shows separate lines for units, main and secondary measurements as well as a dial-type digital bar graph.
The Signet 9900 Transmitter is offered in both panel or field mount versions. Both configurations can run on 12 to 32 power (24 VDC nominal). The 9900 can also be loop-powered with compatible sensors.
Designed for complete flexibility, plug-in modules allow the unit to easily adapt to meet changing customer needs. Optional modules include Relay, Direct Conductivity/Resistivity, H COMM, Batch, 4 to 20mA and a PC COMM configuration tool. The unit can be used with default values for quick and easy programming or can be customized with labeling, adjustable minimum and maximum dial settings, and unit and decimal measurement choices.
- Large auto-sensing backlit display with at-a-glance visibility
- Wastewater Treatment
- Reverse Osmosis
- Deionization
- Chemical Manufacturing/Addition
- Metal and Plastic Finishing
- Fume Scrubbers
- Cooling Towers
- Media Filtration
- Large auto-sensing backlit display with "at-a-glance" visibility
- "Dial-type" digital bar graph
- Intuitive and "user-friendly" interface consistent with legacy Signet ProPoint® and ProcessPro® devices
- Optional Field upgradable relays
- Selectable error mode for current outputs, 3.6mA or 22mA
- 4 to 20 mA input (with optional 8058 Signal Converter)
- Warning LED indicator
- Custom 13-character label capabilities for the channel type
- Factory reset capability
- Relay Module
- Direct Conductivity/Resistivity Module
- H COMM Module
- 4 to 20 Output Module
- Batch Module
- CE
- UL
- CUL
- China RoHS
- RoHS Compliant
- FCC
- Lloyd's Register
| Input Channels | One |
|---|---|
| Input Types Frequency Range | 0.5 to 1500 Hz |
| Input Types Frequency Accuracy | 0.5% of reading |
| Measurement Types | Flow, pH/ORP, Conductivity/Resis tivity, Salinity, Pressure, Temperature, Level, Dissolved Oxygen, Batch or user-defined (via 8058) |
| Case Material | PBT |
| Window | Shatter-resistant Glass |
| Keypad | 4 buttons, injection-molded silicone rubber seal |
| Display | Backlit, 7 and 14-segment |
| Update Rate | 1 s |
| LCD Contrast | 5 Settings |
| Indicators | "Dial-type" digital bar graph. LEDs for Open Collector, Relays and Warning Indicator |
| Enclosure Size | 1/4 DIN |
| Mounting Panel | 1/4 DIN, ribbed on four sides for panel mounting clip inside panel, silicon gasket included |
| Mounting Field | Mounts to standard Signet field mount junction boxes. Optional angle adjustment adapter available |
| Mounting Wall | Large enclosure (sold as an accessory) that encases the panel mount transmitter |
| pH | 0.00 to 15.00 pH |
| pH Temperature | -99 °C to 350 °C (-146 °F to 662 °F) |
| ORP | -1999 to 1999.9 mV |
| Flow Rate | -9999 to 99999 units per second, minute, hour or day |
| Totalizer | 0.00 to 99999999 units |
| Conductivity | 0.0000 to 99999 μS, mS, PPM and PPB (TDS), kΩ, MΩ |
| Conductivity Temperature | -99 °C to 350 °C (-146 °F to 662 °F) |
| Temperature | -99 °C to 350 °C (-146 °F to 662 °F) |
| Pressure | -40 to 1000 psi |
| Level | -9999 to 99999 m, cm, ft, in, % |
| Volume | 0 to 99999 cm3 , m3 , in3 , ft3 , gal, L, lb, kg, % |
| Salinity | 0 to 100 PPT |
| Dissolved Oxygen | PPM 0-50, % SAT 0-200, 0 to 999.9 TORR |
| Dissolved Oxygen Temperature | -99 °C to 350 °C (-146 °F to 662 °F) |
| Backlit LCD | -10 °C to 70 °C (14 °F to 158 °F) |
| Storage Temperature | -10 °C to 70 °C (14 °F to 158 °F) |
| Relative Humidity | 0 to 100% condensing for field mount; 0 to 95% non-condensing for panel mount |
| Maximum Altitude | 4,000 m (13,123 ft) |
| Enclosure Rating | Designed to meet NEMA 4X/IP65 (front face only on panel mount); field mount is 100% NEMA 4X/IP65 |
| Power to Sensors Voltage | +4.9 to 5.5 VDC @ 25 °C, regulated |
| Current | 1.5 mA max in loop power mode (up to 2.0 mA with 24 V @ 300 Ω max. loop impedance); 20 mA max when using DC power |
| Short Circuit | Protected |
| Isolation | Low voltage (< 48V AC/DC) to loop with DC power connected |
| Terminal Blocks Pluggable screw type | 14 AWG max wire gauge |
| Input Power DC | 10.8 to 35.2 VDC, regulated |
| 9900 without Relay Module | 200 mA @ 10.8 VDC to 35.2 VDC |
| 9900 with Relay Module | 300 mA @ 10.8 VDC to 35.2 VDC |
| Overvoltage Protection | 48 Volt Transient Protection Device |
| No DC Power Input Max. Loop Impedance | 50 Ω @ 12 V, 325 Ω @ 18 V, 600 Ω @ 24 V |
| With DC Power Input or with 2nd loop, all the time Max. Loop Impedance | 250 Ω @ 12 V, 500 Ω @ 18 V, 750 Ω @ 24 V |
| Relay Specifications Type | Dry-Contact Relays (2):SPDT, Open Collector (1): N/A |
| Relay Specifications Form | Dry-Contact Relays (2):C, Open Collector (1): N/A |
| Max. Current Rating | Dry-Contact Relays (2):5 A resistive, Open Collector (1): 50 mA DC |
| Max. Voltage Rating | Dry-Contact Relays (2):30 VDC or 250 VAC, Open Collector (1): 30 VDC |
| Hysteresis | Adjustable (absolute in engineering units) (EUs) |
| Latch | Reset in test screen only |
| Delay | 9999.9 seconds (max.) |
| Test Mode | Set On or Off |
| Cycle Time | 99999 seconds (max.) |
| Maximum Pulse Rate | 300 pulses/minute |
| Proportional Pulse | 400 pulses/minute |
| Volumetric Pulse Width | 0.1 to 3200 s |
| Pulse Width Modulation | 0.1 to 320 s |
| Input Types | Digital (S3 L) or AC frequency |
| Input Specifications Digital (S3 L) | Serial ACSII, TTL level, 9600 bps |
| Frequency Input Sensitivity | 80 mV @ 5 Hz, gradually increasing with frequency |
| Frequency Input Span | 0.5 Hz to 1500 Hz @ TTL level input |
| Frequency Input Accuracy | ±0.5% or reading max error @ 25 °C |
| Frequency Input Resolution | 1 μS |
| Frequency Input Repeatability | ±0.2% of reading |
| Power Supply Rejection | ±1 μA per volt |
| Power Supply Short Circuit | Protected |
| Update Rate | (1/frequency) + 150 ms |
| Current Loop Output Standard | ANSI-ISA 50.00.01 Class H |
| Current Output | 4 to 20 mA, isolated, fully adjustable and reversible |
| Span | 3.8 to 21 mA |
| Zero | 4.0 mA factory set; user programmable from 3.8 to 5.0 mA |
| Full Scale | 20.00 mA factory set; user programmable from 19.0 to 21.0 mA |
| Accuracy | ±32 μA max. error @ 25 °C @ 24 VDC |
| Resolution | 6 μA or better |
| Temperature Drift | ±1 μA per °C |
| Power Supply Rejection | ±1 μA per V |
| Isolation | Low voltage (< 48 VAC/DC) |
| Voltage | 12 to 32 VDC ±10% |
| Max. Impedance (with DC power input) | 250 Ω @ 12 VDC/500 Ω @ 18 VDC/750 Ω @ 24 VDC |
| Max. Impedance (no DC power input) | 50 Ω @ 12 VDC/325 Ω @ 18 VDC / 600 Ω @ 24 VDC |
| Update Rate | 150 mS nominal |
| Adjustable Span | Reversible |
| Error Condition | Selectable error condition 3.6 or 22 mA |
| Test Mode | Increment to desired current (range 3.8 to 21.00 mA |
| Open Collector Output | 50 mA DC max., 30 VDC |
| Series | 9900 |
| Type | Flow Controller |